60K BTU Double Code Air - Enthalpy Method Calorimeter ISO 5151
- Brand: global
- Product Code: 60k-btu-air-enthalpy-calorimeter-iso-5151
- Availability: 1000
60K BTU Double Code Air-Enthalpy Method Calorimeter ISO 5151
System introduction:
This air enthalpy method calorimeter lab consists of 1 indoor side room (Room A) and 1 outdoor side room (Room B). The refrigerating capacity, heating capacity and other performances of an air conditioner are tested by means of testing the lab parameters, such as temperature, pressure and electrical performance. This installation can be used to test the performance of various window type, split type, free-standing type and ceiling cassette type and duct type AC air conditioners, and can also be used for other standard operating condition related tests and expanded tests, meeting the need for product sampling inspection and product development. The laboratory is equipped with two stations, which can simultaneously test two sets of 1-Phase prototypes not larger than 30KBtu (to ensure total not large than 60K BTU), if only test one set of prototype once, then prototype can up to 60K BTU, but should not larger than 60K BTU.
In this test system, the operation of the equipment is controlled by a programmable controller and a HMI, test running data are collected by a high accuracy data collector, the data can be transferred at real time to an upper level computer for processing, the computer displays, stores, outputs and prints test reports.
Testing items:
► Rated cooling capacity (T1, T2, T3).
► Rated heating capacity (High, Low, Extra-low)
► Airflow
► Dehumidification capacity
► Input power
► EER(COP)
► Frequency
► Current
► Voltage
Types of UUT and environment:
► Types of unit under test (UUT)
-Split type
-Window type
-Free-standing type
-Ceiling cassette type
-Duct type
-Inver-frequency air condition
► Measurement range of UUT
-Testing Capacity Range:
-Total Cooling Capacity: 6000~60000Btu/h
A station Cooling Capacity: 6000~60000Btu/h
B station Cooling Capacity: 6000~30000Btu/h
-Heating Capacity: 6000~60000Btu/h
A station Heating Capacity: 6000~60000Btu/h
B station Heating Capacity: 6000~30000Btu/h
-Range of air flow:
-Air Flow A : 300~4000 m³/h
Air Flow B : 200~2000 m³/h
-Figure size:Window Type:W:Under 1000mm D:Under 800mm H:Under 1000mm
Split Type:W:Under 1000mm D:Under 500mm H:Under 2000mm
-The electric parameter:
-Single phase power: 0~5kW
-Single phase voltage: 0~300V
-Single phase current: 0~20A
-Frequency: 50/60Hz
-Power factor: 0~1
| Major test conditions | ||||||
| No | Testing Item | Indoor side(℃) | Outdoor side(℃) | |||
| Dry Bulb | Wet Bulb | Dry Bulb | Wet Bulb | |||
| 1 | Rating Cooling | T1 | 27 | 19 | 35 | 24 |
| T2 | 21 | 15 | 27 | 19 | ||
| T3 | 29 | 19 | 46 | 24 | ||
| 2 | Maximum Cooling | T1 | 32 | 23 | 48 | 32 |
| T2 | 27 | 19 | 35 | 24 | ||
| T3 | 32 | 23 | 52 | 31 | ||
| 3 | Freeze-up | T1 | 21 | 15 | 21 | 15 |
| T2 | 21 | 15 | 10 | 8 | ||
| T3 | 21 | 15 | 21 | 15 | ||
| 4 | Minimum Cooling | 21 | 15 | 18 | 12 | |
| 5 | Enclosure Sweat | 27 | 24 | 27 | 24 | |
| 6 | Rating Heating | High | 20 | 15 | 7 | 6 |
| Low | 20 | 15 | 2 | 1 | ||
| Extra Low | 10 | 8 | -5 | -6 | ||
| 7 | Maximum Heating | 27 | 19 | 24 | 18 | |
| 8 | Minimum Heating | 20 | 15 | -7 | -8 | |
| 9 | Automatic Defrost | 20 | 12 | 2 | 1 | |
is a diversified high-tech enterprise integrating testing equipment, scientific research and teaching equipment, and various non-standard customized equipment, integrating independent R&D and design, production and sales, installation and commissioning, and after-sales maintenance. Our technical staff has accumulated a wealth of practical experience.
Maximize the accuracy of your HVAC-R testing with our 60K BTU Double Code Air Enthalpy Calorimeter, designed and manufactured in strict accordance with ISO 5151 and other international testing standards. This advanced test system utilizes the recognized Air Enthalpy Method to measure the cooling and heating capacity of air conditioners, heat pumps, and split systems with unparalleled precision.
Ideal for research laboratories, quality assurance centers, and certification bodies, this calorimeter provides a complete solution for performance rating and energy efficiency verification.
Key Features:
-
Air Enthalpy Method: Precisely calculates capacity by measuring the temperature, humidity, and airflow differential across the indoor unit, delivering accurate performance data without the complexity of refrigerant-side measurement.
-
Dual-Standard Compliance (Double Code): Engineered to meet both ISO 5151 (Non-ducted air conditioners and heat pumps) and other major regional standards (such as AHRI 210/240 or GB/T 7725), ensuring your products are certified for global markets.
-
60K BTU Capacity: Specifically designed to test a wide range of residential and light commercial units, from small window ACs up to 5-ton (60,000 BTU/h) split systems and ducted units.
-
Controlled Environmental Chambers: Includes precisely controlled indoor and outdoor side chambers (psychrometric rooms) that simulate extreme ambient conditions to test unit performance under various climate scenarios.
-
Automated Data Acquisition: Integrated software platform controls the test sequence, monitors all sensors in real-time, and automatically generates comprehensive test reports, reducing human error and test time.
Ensure your cooling products meet the highest standards of efficiency and reliability with our ISO 5151-compliant Air Enthalpy Calorimeter.
Tags: AirEnthalpyCalorimeter, ISO5151, HVACTesting, ACPerformance, Calorimeter, CoolingCapacity, HVACLab, PsychrometricRoom, HeatPumpTesting, TestAndMeasurement